{ "site_id": 1504,
"site_name": "Josh's Sample Boiler Room",
"Specs":
{ "modbus_rtu":
{ "Port1":{
"serial_no":"AQ002Q52",
"baud_rate": 19200,
"parity": "E",
"data_bits": 8,
"stop_bits": 1,
"Devices":{
"Boiler1-knight": {
"device_no": 1,
"device_id": 1501,
"registers": {
"30004": { "name": "System Cascade Setpoint", "type":
"float", "units": "C", "count": 1, "CoV":0.05, "Measure":3, "sensor_id": 150130004, "scale":1,
"signed":0
},
"30005":{ "name": "System Pump Speed", "type": "float", "units": "%", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150130005, "scale":1, "signed":1
},
"30006":{ "name": "Cascade Total Power", "type": "float", "units": "%", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150130006, "scale":1, "signed":1
},
"30008":{ "name": "Outlet Setpoint", "type": "float", "units": "C", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150130008, "scale":0.1, "signed":0
},
"30009":{
"name": "Outlet Temperature", "type": "float", "units": "C", "count": 1, "CoV":0.05, "Measure":3,
"sensor_id": 150130009, "scale":0.1, "signed":0
},
"30010":{ "name": "Inlet Temperature", "type": "float", "units": "C", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150130010, "scale":0.1, "signed":0
},
"30011":{ "name":"Flue Temperature", "type": "float", "units": "C", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150130011, "scale":0.1, "signed":0
},
"40004":{ "name":"Tank SetPoint", "type": "float", "units": "C", "count": 1, "CoV":0.05, "Measure":3,
"sensor_id": 150140004, "scale":0.1, "signed":0
},
"40005":{ "name":"Tank temperature", "type": "float", "units": "C", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150140005, "scale":0.1, "signed":0
},
"40006":{ "name":"Outdoor Temperature", "type": "float", "units": "C", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150140006, "scale":0.1, "signed":0
},
"40007":{ "name":"System Supply Temperature", "type": "float", "units": "C", "count": 1, "CoV":0.05,
"Measure":3, "sensor_id": 150140007, "scale":0.1, "signed":0
}
}
}
}
}
}
}
}