4 changes: 2 additions & 2 deletions fancoil/chiltrix-htp-fancoil-documentation.md
Original file line number Diff line number Diff line change
Expand Up @@ -58,8 +58,8 @@ Vesion 1.0 update:
| 28319 | 6E9F | 03/10 | Whether to use Fahrenheit | (1-℉;0-℃) | DIGI1 |
| 28320 | 6EA0 | 03/10 | Master/Slave | (1-Yes;0-No) | DIGI1 |
| 28321 | 6EA1 | 03/10 | Unit address | (1~99)The default value is 15 | DIGI1 |
| 46801 | B6D1 | 04 | Room temperature | | TEMP1 |
| 46802 | B6D2 | 04 | Coil temperature | | TEMP1 |
| 46801 | B6D1 | 04 | Room temperature | Only 1℃ resolution, but value is in decidegrees C (tenths of a degree) | TEMP1 |
| 46802 | B6D2 | 04 | Coil temperature | Only 1℃ resolution, but value is in decidegrees C (tenths of a degree) | TEMP1 |
| 46803 | B6D3 | 04 | Current fan speed | 0 Off;1 Ultra-low speed; 2 Low speed;3 Medium speed;4 High speed;5 Top speed;6 Auto | DIGI1 |
| 46804 | B6D4 | 04 | Fan revolution | 0~2000 (rpm) | DIGI1 |
| 46805 | B6D5 | 04 | Electromagnetic Valve | 0 Off; 1 On | DIGI1 |