Skip to content
New issue

Have a question about this project? Sign up for a free GitHub account to open an issue and contact its maintainers and the community.

By clicking “Sign up for GitHub”, you agree to our terms of service and privacy statement. We’ll occasionally send you account related emails.

Already on GitHub? Sign in to your account

No matching MIB found for sysOID '.1.3.6.1.4.1.318.1.3.27' #2655

Open
rsiverd opened this issue Oct 10, 2024 · 1 comment
Open

No matching MIB found for sysOID '.1.3.6.1.4.1.318.1.3.27' #2655

rsiverd opened this issue Oct 10, 2024 · 1 comment
Labels
APC impacts-release-2.7.4 Issues reported against NUT release 2.7.4 (maybe vanilla or with minor packaging tweaks) SNMP

Comments

@rsiverd
Copy link

rsiverd commented Oct 10, 2024

Sorry if this is a duplicate. I didn't not see this particular case among the open issues although similar ones exist.

I have a ups.conf configuration with 5 APC UPSes checked via snmp-ups. Four of those UPSes are SMT-1000c and the fifth is SMT-2200c. All of them have NMC cards installed with fairly modern firmware. I can provide more details if needed.

The system runs Ubuntu 22.04.2 LTS with package versions as follows:

$ dpkg -l | grep nut | grep UPS
ii  libnutscan1:amd64                     2.7.4-14ubuntu2                            amd64        network UPS tools - scanner library
ii  nut                                   2.7.4-14ubuntu2                            all          network UPS tools - metapackage
ii  nut-client                            2.7.4-14ubuntu2                            amd64        network UPS tools - clients
ii  nut-server                            2.7.4-14ubuntu2                            amd64        network UPS tools - core system
ii  nut-snmp                              2.7.4-14ubuntu2                            amd64        network UPS tools - SNMP driver

The output of systemctl status suggested an issue that should be reported to NUT developers:

$ systemctl status nut-driver.service
● nut-driver.service - Network UPS Tools - power device driver controller
     Loaded: loaded (/lib/systemd/system/nut-driver.service; static)
     Active: active (running) since Thu 2024-10-10 13:19:36 HST; 17s ago
    Process: 27216 ExecStart=/sbin/upsdrvctl start (code=exited, status=0/SUCCESS)
      Tasks: 5 (limit: 154514)
     Memory: 7.6M
        CPU: 87ms
     CGroup: /system.slice/nut-driver.service
             ├─27218 /lib/nut/snmp-ups -a adminups-snmp
             ├─27220 /lib/nut/snmp-ups -a ashups-snmp
             ├─27222 /lib/nut/snmp-ups -a chillups-snmp
             ├─27224 /lib/nut/snmp-ups -a domeups-snmp
             └─27226 /lib/nut/snmp-ups -a telups-snmp

Oct 10 13:19:34 proc4 snmp-ups[27224]: Startup successful
Oct 10 13:19:34 proc4 upsdrvctl[27225]: No matching MIB found for sysOID '.1.3.6.1.4.1.318.1.3.27'!
Oct 10 13:19:34 proc4 upsdrvctl[27225]: Please report it to NUT developers, with an 'upsc' output for your device.
Oct 10 13:19:34 proc4 upsdrvctl[27225]: Going back to the classic MIB detection method.
Oct 10 13:19:34 proc4 upsdrvctl[27225]: Detected Smart-UPS 1000 on host 10.10.10.37 (mib: apcc 1.2)
Oct 10 13:19:35 proc4 upsdrvctl[27225]: [telups-snmp] Warning: excessive poll failures, limiting error reporting (OID = .1.3.6.1.4.1.318.1.1.1.9.2.3.1.5.1.1.3)
Oct 10 13:19:35 proc4 upsdrvctl[27225]: [telups-snmp] Warning: excessive poll failures, limiting error reporting (OID = .1.3.6.1.4.1.318.1.1.1.9.3.3.1.6.1.1.1)
Oct 10 13:19:36 proc4 snmp-ups[27226]: Startup successful
Oct 10 13:19:36 proc4 upsdrvctl[27216]: Network UPS Tools - UPS driver controller 2.7.4
Oct 10 13:19:36 proc4 systemd[1]: Started Network UPS Tools - power device driver controller.

I checked individually and see this error during startup for both models of UPS. The nut-snmp driver seems to have no trouble sorting out content though.

$ upsc telups-snmp
Init SSL without certificate database
battery.charge: 100.00
battery.date: 2023-02-22
battery.runtime: 1616.00
battery.runtime.low: 120
battery.voltage: 26.20
device.mfr: APC
device.model: Smart-UPS 1000
device.serial: 3S2211X28903
device.type: ups
driver.name: snmp-ups
driver.parameter.pollinterval: 15
driver.parameter.port: 10.10.10.37
driver.parameter.synchronous: no
driver.version: 2.7.4
driver.version.data: apcc MIB 1.2
driver.version.internal: 0.97
input.frequency: 59.80
input.sensitivity: low
input.transfer.high: 136
input.transfer.low: 97
input.transfer.reason: selfTest
input.voltage: 119.80
input.voltage.maximum: 120.20
input.voltage.minimum: 118.50
output.current: 2.30
output.frequency: 59.80
output.voltage: 119.80
output.voltage.nominal: 120
ups.firmware: UPS 06.0 (ID1027) 
ups.id: telups
ups.load: 38.20
ups.mfr: APC
ups.mfr.date: 2022-11-03
ups.model: Smart-UPS 1000
ups.serial: 3S2211X28903
ups.status: OL
ups.temperature: 26.20
ups.test.date: 09/28/2024
ups.test.result: Ok
@desertwitch
Copy link
Contributor

NUT 2.7.4. is 8 years old at this point, please check if you can't get a newer version installed on your OS.
e.g. https://launchpad.net/ubuntu/+source/nut or manually compiling it, there's tons of useful changes in later versions.

@jimklimov jimklimov added APC SNMP impacts-release-2.7.4 Issues reported against NUT release 2.7.4 (maybe vanilla or with minor packaging tweaks) labels Oct 11, 2024
Sign up for free to join this conversation on GitHub. Already have an account? Sign in to comment
Labels
APC impacts-release-2.7.4 Issues reported against NUT release 2.7.4 (maybe vanilla or with minor packaging tweaks) SNMP
Projects
Status: Todo
Development

No branches or pull requests

3 participants