pid-complete

A node-red node to perform PID Calculations and autotuning.

Getting started

This node is under active development and may have lots of bugs and breaking changes. I will release on NPM once I deem it stable.

pid-complete node

This node is a PID controller that is easy to implement into your flow, but gives you enough options to control complex systems. This implementation uses the parallel (ideal) form of the PID equation instead of the classical form. This means that the system uses three gains (kp, ki, and kd) as opposed to one gain and two times (kp, ti, and td) - this is a design choice of this library.

If you setup your Node Red context stores to have at least one store saved to the filesystem, you can configure the PID node save it's gains in global context that is saved across re-deploys and re-boots. Setting up a persistent context store is not required to use this library, but without persistent storage, you must initialize kp, ki, and kd on every re-deploy or re-boot.

Inputs

  1. msg.payload - must contain the input process variable (PV) unless a command is sent or valid topic is set.
  2. msg.cmd - can contain reset, disable, auto, or manual.
  3. msg.topic - can contain no topic or can contain sp, kp, ki, or kd with the new setpoint or gain setting in msg.payload.

Output

  1. msg.topic - contains the name of the node.
  2. msg.payload - contains the output value if in auto or manual.
  3. msg.proportional - contains the output of the last proportional calculation.
  4. msg.integral - contains the output of the last integral calculation.
  5. msg.derivative - contains the output of the last derivative calculation.

Configuration

Setting Description
Name Whatever you name the node. Will be used as topic of node output.
Calculation Interval Time between calculations. If set faster than inject interval, node will calculate new input on every inject. If set slower than inject interval, node will wait until next inject after calculation interval has elapsed. Set this long if changing the control output quickly would damage the system (e.g. valve packing wearing out from quick control oscillations)
Max Output - Decreasing PV Sets the largest control output that produces a decreasing PV. Can be any number, positive or negative.
Max Output - Increasing PV Sets the largest control output that produces an increasing PV. Can be any number, positive or negative.
Output When Disabled Default control output when in Disabled mode.
Proportional on Measurement Calculates proportional term from measurement instead of from error.
Derivative on Measurement Calculates derivative term from measurement instead of from error.
Persistent Context Store The name of the context store that is configured for filesystem storage.

Context Store Setup

If you want to setup persistent storage across re-deploys, you need to change your Node-Red settings.js file to set up a filesystem based context store. Instructions can be found at https://nodered.org/docs/user-guide/context#using-multiple-context-stores.

Advanced Details

When setting msg.cmd to manual, you can either include the desired manual output to msg.payload or you can leave it empty which will set the manual output to the last output. The last output value is either the last calculated PID value when in auto mode or Output When Disabled when in disable mode.

When setting msg.cmd to auto when currently in manual, the manual output will be set into the integral term to provide bumpless transition. If msg.cmd is set to auto while currently in auto mode, the integral term will not be reset. The only way to reset the integral term is to either set msg.cmd to reset or cycle the node into disable then back to auto which will reset the integral term to Output When Disabled. To change the manual setpoint, you must resend msg.cmd with manual and the desired output in msg.payload.

Setting msg.cmd to reset will reset the integral term, but will not change the current mode.

Note that the Proportional, Integral, and Derivative outputs only send values when in auto mode. You do not need to keep track of these values, but they can be useful for visualization and tuning purposes.

For many applications, including heating applications, Max Output - Decreasing PV will be set to 0 and Max Output - Increasing PV will be set to the maximum safe output value. For other applications, including cooling applications, the Max Output - Increasing PV will be 0 and Max Output - Decreasing PV will be the maximum safe output value. For applications that heat and cool, it is common to set a positive and negative range centered at 0. In this case you would separate the positive from negative value outside of the PID node. These are just recommendations and you can choose any arbitrary range that makes your system work.

This node guarantees that the value sent in output will never fall outside of the range set by Max Output - Decreasing PV and Max Output - Increasing PV regardless of what mode of operation it is in. A commanded manual setpoint outside of the range will be capped at the closest allowable value.

pid-complete-autotune node

This node should wire directly between all of your inputs and the PID node. This will sniff the values that it needs (e.g. current state, current setpoint, current PV, etc.) and pass all messages through to the PID node. When you send the command to start autotuning, this node will calculate a hysteresis value based on the Bump Percent and setpoint and then go through the following steps:

  1. Set PID Node to Manual
  2. If the PV is higher than setpoint - hysteresis, set the control output to Max Output - Decreasing PV until the PV is below setpoint - hysteresis
  3. Set the control output to Max Output - Increasing PV until the PV is above setpoint + hysteresis
  4. Set the control output to Max Output - Decreasing PV until the PV is below setpoint - hysteresis
  5. Repeat steps 3-4 twice while recording the time and value of the max and min PV during each high and low peak
  6. Calculate the PID parameters

Basic PID tuning uses two parameters and a set of tuning rules to calculate the three gains. The parameters are the ultimate gain and the ultimate period. These can be found manually by setting ki and kd to 0 and slowly increasing kp until the PV just starts to oscillate, that is your ultimate gain (ku). You can then measure the period of the oscillations, that is your ultimate period (pu). This autotune node does a simpler test which forces oscillations manually and then measures the commanded amplitude of oscillations vs the actual recorded amplitude and the period of oscillations. This method is not perfect and it is not fast, but is a good starting point to manually tweak your settings. The PID gains are then calculated by using the below tuning rules and equations.

Rule kp ki kd
Ziegler-Nichols PID 0.60 * ku kp / (0.50 * pu) kp * (0.125 * pu)
Ziegler-Nichols PI 0.45 * ku kp / (0.833 * pu) 0
Ziegler-Nichols PD 0.80 * ku 0 kp * (0.125 * pu)
Pessen-Integral 0.70 * ku kp / (0.40 * pu) kp * (0.333 * pu)
Some Overshoot 0.333 * ku kp / (0.50 * pu) kp * (0.333 * pu)
No Overshoot 0.20 * ku kp / (0.50 * pu) kp * (0.333 * pu)

Input

  1. msg.payload - must contain the input process variable (PV) unless a command is send.
  2. msg.cmd - autotune starts the autotuning process. Any other valid msg.cmd cancels the autotune.

Output

This node passes through all messages except msg.cmd= autotune which starts autotuning and places the pid-complete node in manual control.

When the autotune completes successfully, the node sends a series of messages to set the kp, ki, and kd. These values are not saved in the PID node, so it is a good practice to intercept these values and save them in persistent storage within your node if that is important to your system.

Configuration

Setting Description
Name What ever you name the node.
Output - Decreasing PV Sets the largest control ouput that produces a decreasing PV.
Output - Increasing PV Sets the largest control output that produces an increasing PV.
Output When Disabled Default control output when in Disabled mode.
Tuning Rule Sets the autotuning parameters to be used.
State after Tuning Does the autotune set the PID controller to disabled, manual, auto, or whatever it was previously set to after successful tuning
Autotune Bump Percent The hysteresis value used in tuning to separate the max and min peaks, specified as percent of setpoint.

Contributing

  1. Fork this repo
  2. Write a red unit test for your change
  3. Implement the code and make the test green
  4. Refactor your code to make it nice
  5. Make a pull request

License

This software is licensed under an MIT license. Portions of this software are ported and modified from other works credited below which bear an MIT License and BSD license respectively. See the licenses folder of this repository for reproductions of the original licenses from the source material.