Building Ontology Additions #1496
Conversation
@@ -157,6 +157,17 @@ VAV_SD_DSP_HWZC: | |||
- DSP | |||
- HWZC | |||
|
|||
VAV_SD_DSP_HWZC_ZSPM: | |||
guid: "c8340b79-25be-43b1-8d4b-afd404d0ebc5" | |||
description: "Single duct reheat VAV with dual setpoint control." |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Please add zone static pressure monitoring to description.
|
||
HX_CWDT_PRWDT_CWSISOVPM_CWBYPVPM: | ||
guid: "e8d28beb-539f-404e-9af8-96e9d6926908" | ||
description: 'Condenser/chilled water heat exchanger.' |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Please change to condenser/process
@@ -118,6 +118,42 @@ HX_CWDT_CHWDT_CWRISOVPM: | |||
- CHWDT | |||
- CWRISOVPM | |||
|
|||
HX_CWDT_PRWDT_CWSISOVPM: | |||
guid: "6f180176-dde9-4321-a198-9f1ab3d637de" | |||
description: 'Condenser/chilled water heat exchanger.' |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Please change to condenser/process
@@ -252,6 +252,16 @@ HWS_SWTC_BYPVPM_WDPC_WFRC: | |||
- WDPC | |||
- WFRC | |||
|
|||
HWS_SWTC_WDPC_BYPVFRC: | |||
guid: "67154932-688a-4c74-b797-62b6c5fa29ae" | |||
description: "Heating water system (temp/pressure control) with bypass control and flow monitoring." |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
Please change to "with bypass valve flowrate control"
@@ -586,6 +605,19 @@ CHWS_SWTC_WDPC_BYPVFRC_WSEBYPVM_MCBYPVM: | |||
- WSEBYPVM | |||
- MCBYPVM | |||
|
|||
CHWS_SWTC_WDPC_BYPVFRC_MCBYPVM_MCSWFRM_MMCWDPC: | |||
guid: "a8689543-c41a-4de2-af1f-2005bcb65172" | |||
description: "Chilled water system with differential pressure control, mechanical cooling bypass and waterside economizer bypass." |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
there is no WSE bypass
@@ -150,6 +150,19 @@ CDWS_CLPM_SWTC_WDPM_WFRC: | |||
- WDPM | |||
- WFRC | |||
|
|||
CDWS_SWTC_WDPC_WFRC_RWISOVM_MWFRM_BWFRM: | |||
guid: "d59e0ced-f678-43b0-96cd-8c92951c1cb7" | |||
description: "Condensing water system with supply temperature and flowrate control as well as thermal power and differential pressure control." |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
there is no thermal power monitoring
|
||
AHU_DFSS_DFVSC_EFSS_EFVSC_DX4DC_ECONM_EDBPC_BSPC_DSPC: | ||
guid: "156e5ec6-5d1f-4571-9857-cf90d0baa1f6" | ||
description: "Multi-zone AHU with exhaust damper monitoring" |
There was a problem hiding this comment.
Choose a reason for hiding this comment
The reason will be displayed to describe this comment to others. Learn more.
I think it's more like "exhaust damper building pressure control"
@shambergoldstein @ccquigley ready for your review! Thank you! |
@shambergoldstein This is ready for another review from your comments. |
@shambergoldstein Ready for review. I removed the Noncanonical type and replaced it with FCU_CSP_DFSS_DXDDC_RMM. |
Changes affecting some new subfields, abstracts, and several general types.